• 12kV indoor high-voltage load break switch
12kV indoor high-voltage load break switch
discuss personally
Model
FN5 - 12
Basic info
Brand ROCKWILL
Model NO. 12kV indoor high-voltage load break switch
Rated voltage 12kV
Rated normal current 400A
Rated frequency 50/60Hz
Series FN
Product Detail

Product Overview

The FN5 - 12 indoor AC high - voltage load break switch (hereinafter referred to as the load break switch) is suitable for AC 50Hz, 12kV networks. It is used for breaking load current and closing short - circuit current. The load break switch with a fuse can cut off short - circuit current and be used as a protection switch.

This load break switch can be equipped with the CS6 - 1 manual operating mechanism and the special CS manual operating mechanism for this product.

Key Features

  • Precise Current Control:Suitable for 12kV, 50Hz AC systems. It can stably break load current and close short - circuit current, ensuring normal operation and maintenance of the power grid as well as emergency operations during faults.

  • Extended Protection Function:When paired with a fuse, it can cut off short - circuit current and act as a protection switch, providing overload and short - circuit dual protection for power equipment and simplifying the protection levels of the distribution network.

  • Wide Scene Adaptability:Focused on indoor 12kV AC networks. It is suitable for typical indoor power distribution scenarios such as ring main units and box - type substations, meeting the needs of distribution network construction.

  • Flexible Mechanism Configuration:Supports the CS6 - 1 general manual operating mechanism and can also be adapted to the special CS mechanism, compatible with different operating habits and equipment matching requirements.

  • Mature Technical Architecture:Iterated based on the classic FN5 - 12 model. It has a compact structure, stable arc - extinguishing performance, high long - term operation reliability, and reduces operation and maintenance costs.

Technical Parameters

Name

Unit

Value

Rated Voltage

kV

12

Maximum Operating Voltage

kV

12

Rated Frequency

Hz

50

Name

Unit

Value

Rated Current

A

400

630

Rated Short - time Withstand Current (Thermal Stable Current)

kA/S

12.5/4

20/2

Rated Peak Withstand Current (Dynamic Stable Current)

kA

31.5

50

Rated Closed - loop Breaking Current

A

400

630

Rated Active Load Breaking Current

A

400

630

5% Rated Active Load Breaking Current

A

20

31.5

Rated Cable Charging Breaking Current

A

10

Rated No - load Transformer Breaking Current


No - load Current of 1250kVA Transformer

Rated Short - circuit Making Current

kA

31.5

50

Load Current Breaking Times

Load/Time

100%/20
60%/35

30%/75
5%/80

1min Power Frequency Withstand Voltage (Effective Value, to Ground, Phase - to - Phase/Isolation Break)

kV

42/48

Power Frequency Withstand Voltage, Between Isolation Breaks

kV

53

Lightning Impulse Withstand Voltage (Peak Value, to Ground, Phase - to - Phase/Isolation Break)

kV

75/85

Opening and Closing Operating Torque (Force)

N·m (N)

90(80)

100(200)

Technical Parameters of Fuse

Model

Rated Voltage (kV)

Rated Current of Fuse (A)

Rated Breaking Current (kA)

Rated Current of Fuse Element (A)

RN3

 

12

 

50

12.5

2, 3, 5, 7.5, 12, 15, 20, 30, 40, 50

75

12.5

75

100

12.5

100

200

12.5

150, 200

SDL*J

12

40

50

6.3, 10, 16, 20, 25, 31.5, 40

SFL*J

12

100

50

50, 63, 71, 80, 100

SKL*J

12

126

50

125

Operating Environmental Conditions

  • Altitude: Not exceeding 1000m;

  • Ambient Air Temperature: Upper limit +40°C, Lower limit -25°C (Not lower than -5°C for motor - operated mechanisms);

  • Relative Humidity: Daily average not greater than 95%, Monthly average not greater than 90% (+25°C);

  • Ambient air should be free from obvious pollution by corrosive or flammable gases, water vapor, etc.;

  • No frequent severe vibration.

Know your supplier
ROCKWILL
Rockwill Electric Group Global Manufacturer of High voltage and medium-voltage power equipment and smart grid solutions. Headquartered in Wenzhou, China. Serving 100+ countries with quality, innovation, and trust. What We Offer: • HV-MV switchgear (VCB, SF₆ circuit breakers, RMU, GIS) • Distribution transformers and substations • Smart grid and monitoring systems • Solar, wind, EV charging, and energy storage solutions • EPC turnkey power projects Certified: ISO 9001 / ISO 14001 / ISO 45001
Main Categories
High voltage
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$150,000,000
Professional Experience
16 years
Workplace
108000m²m²
占位
占位
Related Products
Related Knowledges
Installation and Commissioning of 10kV Dry-Type Transformers
Installation and Commissioning of 10kV Dry-Type Transformers
By James, 10 Years of Electrical Equipment Maintenance ExperienceHi everyone, I’m James, and I’ve been working in electrical equipment fault repair for 10 years.Over the past decade, I’ve worked in factories, substations, and distribution rooms of all sizes, involved in the installation, commissioning, maintenance, and troubleshooting of dry-type transformers. Dry-type transformers are among the most common electrical devices we deal with on a daily basis.Today, a new colleague
James
07/01/2025
What are the reasons for low insulation at the low-voltage side of a dry-type transformer?
What are the reasons for low insulation at the low-voltage side of a dry-type transformer?
Hi everyone, I’m Felix, and I’ve been working in electrical equipment fault repair for 15 years.Over these years, I’ve traveled across factories, substations, and distribution rooms all over the country, troubleshooting and repairing all kinds of electrical equipment. Dry-type transformers are among the most common devices we deal with.Today, a friend asked me:“What does it mean when the low-voltage side of a dry-type transformer has low insulation resistance?”Great
Felix Spark
07/01/2025
What tests are required for dry-type transformers?
What tests are required for dry-type transformers?
1 Pre - commissioning InspectionAs a front - line tester, before formally commissioning a dry - type transformer, I need to carry out a comprehensive and systematic inspection. First, I conduct a visual inspection of the transformer body and its accessories, carefully checking for mechanical damage or deformation. Then, I check whether the leads of the high - and low - voltage windings are firmly connected and whether the bolt tightening torque meets the standard requirements (usually 40 - 60N&m
Oliver Watts
07/01/2025
What aspects need attention during the installation of dry-type transformers?
What aspects need attention during the installation of dry-type transformers?
1 Pre - installation PreparationAs a front - line installer, I know very well that the preparation work before installing a dry - type transformer must be thorough. First, I will carefully review the design drawings and technical documents, and check one by one the technical parameters such as the model specification, rated capacity, and voltage level of the transformer to ensure they are in full compliance with the design requirements. Then, I will conduct an unpacking inspection of the transfo
James
07/01/2025
What are the causes of dry-type transformers burning out during operation?
What are the causes of dry-type transformers burning out during operation?
1 Fault PhenomenonI am engaged in front - line fault maintenance work, and recently encountered problems with dry - type transformers. Dry - type transformers have a simple structure, are convenient for transportation, and easy for maintenance. They are widely used in power distribution places with relatively high environmental protection requirements. Because of their good fire - resistance, they can be installed in load - center areas to reduce voltage loss and power loss.The property manageme
Felix Spark
07/01/2025
Method for Automatic Isolation of Customer Equipment Faults by Load Switches in Distribution Networks
Method for Automatic Isolation of Customer Equipment Faults by Load Switches in Distribution Networks
1 OverviewDistribution network safety has long been under - addressed, with its automation lagging substation automation . Using 10 kV intervals of existing substations to set line section points meets future grid needs . Configuration of distribution switches, section switches, and protection must match substation outgoing - line protection for reliability. Fault isolation, self - healing, and restoration are key to distribution automation .Scholars have studied smart distribution network fault
Felix Spark
06/30/2025
×
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!