• 40.5(72.5)kV Hybrid Type HV Gas-Insulated Switchgear(GIS)
40.5(72.5)kV Hybrid Type HV Gas-Insulated Switchgear(GIS)
discuss personally
Model
ZHW58A-72.5/4000-40
ZHW58A-72.5/3150-31.5
ZHW58A-40.5/4000-40
ZHW58A-40.5/2500-31.5
Basic info
Brand Wone
Model NO. 40.5(72.5)kV Hybrid GIS
Rated voltage 72.5kV
Rated normal current 2500A
Rated frequency 50/60Hz
Rated short circuit breaking current 31.5kA
Series ZHW58A-40.5(72.5)
Product Detail

Product introduction:

ZHW58A series was originally designed to meet the needs of power construction and hybrid product development, and its main application scenario is to meet the needs of 35-500KV substation expansion; At present, ZHW58A-40.5/72.5 products have reached the leading level at home and abroad in terms of technical advancement and quality reliability.

Main characteristic:

  •  Current transformers, isolation, grounding switch combination, compact, lightweight design, which can realize the whole transportation, save area, relative AlS station save covers an area of 70%, suitable for power plant and substation construction, expansion or reconstruction project and railway electrification construction, especially suitable for old substation upgrading, reduce the construction difficulty and investment scale.

  • CT is arranged on two sides of the circuit breaker (different from the structure of mainstream manufacturer’s' similar products, complying with the requirement "blind area of main protection shall be avoided in the configuration of protective current transformer and the allocation of secondary winding" as specified in the Technical specifications of Relay Protection and Safety Automatic Device, improving the reliability of power supply.

  • The product also adopts straight-through CT, completely solving problems such as excess moisture and low insulation margin and promoting the insulation resistance and reliability of the product.

  •  The product is configured with a grounding switch on equipment side and line side in a built-in way, with reliable earthing that prevents safety hazards in maintenance.

  • The circuit breaker adopts light-spring operating mechanism and aluminum frame of integral casting. It’s closing-opening springs adopt spiral dual-pressure spring, with a compact and indefatigable structure, realizing a mechanical life of 10000compressions.

  •  Aviation plugs are used to connect CB, DES & ES mechanism cases and control cabinet, facilitating field installation and commissioning.

  •  The structure of three-position disconnecting/grounding switch is stable and reliable.

  •  The inlet and outlet lines are connected to the equipment through bushings. Composite insulation bushings and porcelain bushings can be selected., Compared with GlS equipment, the enclosed bushings are omitted, and theSF6 gas consumption is less (less than 50% of GiS consumption), which is green and economical.

Main technical parameters:

image.png

Order Notice:

  • Application working condition (incoming/outgoing line, main transformer or PT interval);

  • Rated electrical parameters (voltage, current, breaking current and so on);

  • Conditions of use environment (ambient temperature, altitude and class of environmental pollution);

  • Control voltage of operating mechanism and motor voltage;

  • Quantity. current ratio, grade combination and secondary load of current transformer;

  • Name and quantity of spare products, spare parts & special tools and equipment (to be ordered separately).

What are the structural characteristics of hybrid high-voltage gas-insulated switchgear? 

Hybrid Gas Insulation System:

  • Typically, a mixture of SF₆ and other gases (such as N₂, CF₄, etc.) is used as the insulating medium. This design aims to combine the properties of different gases. For example, SF₆ has excellent insulating and arc-quenching properties but poses environmental concerns due to its greenhouse effect. By mixing it with other gases, the amount of SF₆ can be reduced while maintaining good insulation performance. The insulation system consists of sealed gas compartments that enclose the high-voltage conductive parts, preventing contact with the external environment and ensuring reliable electrical insulation.

Compact Design Layout:

  • To fully utilize the insulating properties of the hybrid gas, the internal structure of the equipment is designed to be compact. Various components of the switchgear, such as circuit breakers, disconnect switches, earthing switches, and busbars, are carefully arranged to minimize the overall size of the equipment. For example, compact circuit breaker designs and optimized busbar layouts enable efficient electrical connections and functional integration within a limited space.

Reliable Sealing Structure:

  • To ensure good insulation performance, the hybrid gas must be maintained at specific pressure and purity levels. Therefore, the equipment features highly reliable sealing structures. High-quality sealing materials (such as rubber O-rings, metal gaskets, etc.) and sealing techniques are used to ensure the airtightness of the gas compartments and prevent gas leakage. Additionally, the sealing structure must withstand temperature changes, mechanical vibrations, and other factors, maintaining stable sealing performance over the long term.


Know your supplier
Wone
Main Categories
High voltage/Low voltage/Wire cable/Instrument meters/New energy/Tester/Production equipment/Generator/Electrical fittings/Integrated Electrical Equipment
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$50,000,000
Professional Experience
1 years
Workplace
65666m²m²
占位
占位
Related Products
Related Knowledges
Modular Intelligent Substation - Prefabricated Secondary Switchgear Integration Assembly
Modular Intelligent Substation - Prefabricated Secondary Switchgear Integration Assembly
With the development of the national economy and society, the requirements for the quality and craftsmanship of power grid projects have become increasingly stringent. The need to improve the construction progress and quality of substations has created opportunities for the promotion of prefabricated cabin - type intelligent substations. The traditional on - site wiring and commissioning of secondary substation equipment involve a large amount of work. Moreover, on - site construction has to wai
Echo
06/13/2025
Application of Pre-integrated Prefabricated Substations in Renewable Energy Sector
Application of Pre-integrated Prefabricated Substations in Renewable Energy Sector
Against the backdrop of profound changes in the global energy landscape and the booming development of the new energy industry, the construction mode of traditional substations struggles to meet the rapid deployment needs of new energy projects. The modular intelligent prefabricated cabin substation, leveraging its innovative advantages, has become a key direction for optimizing the new energy power system. In - depth exploration of its technical principles, industry adaptability, and applicatio
Echo
06/13/2025
Research on Reliability Enhancement Scheme Implementation for Modular Intelligent Prefabricated Substations
Research on Reliability Enhancement Scheme Implementation for Modular Intelligent Prefabricated Substations
1 Implementation Strategies for the Scheme1.1 Deepen Survey and ResearchBefore constructing prefabricated cabin - type substations, it is necessary to conduct detailed surveys of local working conditions, clarify the construction scale and objectives, evaluate existing power facilities, plan projects, make up for infrastructure shortcomings, and adjust the construction rhythm. Meanwhile, control costs to avoid project suspension.1.2 Strengthen Structural ConstructionDuring promotion, multi - dim
Echo
06/13/2025
Comparative Analysis of 500 kV Prefabricated Substations vs. Conventional Substations
Comparative Analysis of 500 kV Prefabricated Substations vs. Conventional Substations
The secondary equipment area of conventional substations uses reinforced concrete or prefabricated steel structures, facing issues like long construction cycles, unreasonable functional zone design, strict environmental assessments, dust, noise, and disturbances. Primary and secondary equipment can only be installed after civil works and decoration, lowering construction efficiency.Prefabricated cabin substations integrate modularity, intelligence, and cost - effectiveness, boasting green, energ
Dyson
06/13/2025
Operational Analysis of Prefabricated Enclosure Substations in Extreme Cold Climate Applications
Operational Analysis of Prefabricated Enclosure Substations in Extreme Cold Climate Applications
Under global climate diversity, alpine power construction faces technical and environmental challenges. Extreme climates, complex geology, and long - term low winter temperatures, along with ice, snow, and storms, strain electrical equipment stability and power facility construction (schedule, cost, maintenance). Traditional on - site substations, with long construction and poor adaptability, can’t meet alpine regions’ fast, stable power needs.Prefabricated cabin substations, as modu
Echo
06/13/2025
Implementation of Precast Foundations for Ring-Main Unit Compact Substations in Grid Modernization Initiatives
Implementation of Precast Foundations for Ring-Main Unit Compact Substations in Grid Modernization Initiatives
Compact substation boxes, with advantages like safe operation, high reliability, and easy maintenance, are used in urban grid construction/renovation. Structurally divided into American - style (high - cost, noisy, low - efficiency, gradually phased out) and European - style (large - sized but more advantages, still popular).To address their pros/cons, ring - network prefabricated ones were developed.I. Basic Materials for Prefabricated Compact Substation BoxesMaterials need hardness, strength,
Echo
06/13/2025
×
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!