Resistance & Reactance Grounding

Encyclopedia
04/29/2025

Resistance Grounding

In resistance grounding, the neutral of the electrical system is linked to the ground via one or multiple resistors. This grounding method serves to restrict fault currents, safeguarding the system against transient overvoltages. By doing so, it reduces the risk of arcing grounds and enables effective ground - fault protection.

The resistance value employed in a neutral grounding system is critical. As illustrated in the figure below, it should be neither excessively high nor too low. An overly high resistance may compromise the effectiveness of fault current limitation, while an extremely low resistance might not adequately protect the system from transient overvoltages and could increase the risk of arcing faults.

image.png

If the resistance value is extremely low, the system effectively functions as a solidly grounded one. Conversely, when the resistance is extremely high, the system behaves as if it were ungrounded. The ideal resistance value is carefully selected to strike a balance: it must limit the ground - fault current, yet ensure that enough ground current still flows to enable the proper operation of ground - fault protection devices. Generally, the ground - fault current can be restricted to a range of 5% to 20% of the current that would occur during a three - phase line fault.

Reactance Grounding

In a reactance - grounded system, as depicted in the figure below, a reactance component is inserted between the neutral point and the ground. This insertion serves the purpose of limiting the fault current, providing a means to control and manage electrical faults within the system.

image.png

In a reactance - grounded system, to effectively reduce transient overvoltages, it is essential that the ground - fault current not fall below 25% of the three - phase fault current. This requirement represents a significantly higher minimum current threshold compared to what is typically desired in a resistance - grounded system. This distinction highlights the different operational characteristics and design considerations between the two grounding methods, emphasizing the unique role of reactance grounding in safeguarding the electrical system against potentially damaging transient overvoltages.

Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Effects of Electric Current on Human Body
Effects of Electric Current on Human Body
When an electrical current traverses the human body, the nervous system endures an electric shock. The severity of this shock predominantly hinges on three key factors: the magnitude of the current, the pathway the current follows through the body, and the duration of contact. In the most severe instances, the shock disrupts the normal functioning of the heart and lungs, potentially leading to unconsciousness or even death.It is generally accepted that currents below 5 milliamperes (mA) pose min
Edwiin
05/22/2025
What is Automatic Voltage Regulator?
What is Automatic Voltage Regulator?
An automatic voltage regulator is employed to regulate voltage, converting fluctuating voltages into a constant one. Voltage fluctuations mainly stem from variations in the load on the supply system. Such voltage variations can damage the equipment within the power system. These fluctuations can be mitigated by installing voltage - control equipment at various locations, such as near transformers, generators, and feeders. Multiple voltage regulators are often placed throughout the power system t
Edwiin
05/22/2025
What is Static Voltage Regulator?
What is Static Voltage Regulator?
Types of Static Voltage RegulatorThe static voltage regulator is superior to electromechanical regulators in respect of the accuracy of control, response, reliability and maintenance. The static voltage regulator is mainly classified into two types. They are;Servo Type Voltage RegulatorMagnetic Amplifier RegulatorThe types of static voltage regulator are described below in details;Servo Type Voltage RegulatorThe main feature of the servo type voltage regulator is the use of the amplidyne. The am
Edwiin
05/21/2025
What is Arc Extinction Circuit Breaker?
What is Arc Extinction Circuit Breaker?
When the current-carrying contacts of a circuit breaker separate, an arc forms and persists briefly after contact separation. This arc is hazardous due to the heat energy it generates, which can produce explosive forces.A circuit breaker must extinguish the arc without damaging equipment or endangering personnel. The arc significantly influences the breaker’s performance. Interrupting aDC arcis inherently more challenging than anAC arc. In an AC arc, the current naturally reaches zero duri
Edwiin
05/20/2025
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!