What Are the Steps for Error Testing GIS Voltage Transformers?

Oliver Watts
07/08/2025

Hey everyone, I'm Oliver, and I've been working with current transformers (CTs) and voltage transformers (VTs) for 8 years.

From assisting my mentor on site to leading high-voltage testing teams and conducting error calibrations independently, I’ve dealt with all kinds of instrument transformers — especially those used in GIS systems. The error test for voltage transformers is something I perform regularly.

A few days ago, a friend asked me:

“Oliver, how exactly do you perform an error test on a GIS voltage transformer? What’s the process?”

That’s a super practical question! So today, I want to share with you:

What are the actual steps involved in testing the error of a GIS voltage transformer — and what should you watch out for?

No complicated jargon — just plain, real-world talk based on my hands-on experience over the past eight years. Let’s get into it!

1. What Is a VT Error Test?

Simply put, an error test checks whether the output voltage of the VT matches the actual input voltage — in other words, how accurate the transformer really is.

If the error is too large:

  • The metering data will be off, which affects billing.
  • Protection devices might misinterpret signals and either trip unnecessarily or fail to operate when needed.

So this isn’t just a formality — it’s a critical check.

2. Preparation Before the Test
2.1 Clarify the Purpose

Are you testing for factory acceptance, commissioning, or routine maintenance? Each case may have slightly different requirements.

2.2 Check Connections and Safety

  • Ensure the primary side of the VT is de-energized and properly grounded.
  • Confirm secondary wiring is correct.
  • Make sure your test equipment — like the voltage booster, standard VT, and error tester — is in good condition and within calibration period.

2.3 Prepare Reference Equipment

You’ll usually need a high-accuracy reference voltage transformer to compare against the one being tested.

2.4 Step-by-Step Testing Procedure
Step 1: Set Up the Test Circuit

  • Connect the primary side to the voltage source.
  • Connect both the test VT and the standard VT in parallel.
  • Connect the secondary outputs to the error tester.

Important: Make sure the polarity is correct — otherwise, errors will be exaggerated or the test will fail outright.

Step 2: Slowly Raise the Voltage to Rated Level

  • Increase voltage gradually and evenly.
  • Watch for any unusual sounds or signs of discharge.
  • Once rated voltage is reached, let it stabilize for a moment.

Step 3: Record the Error Data

At rated voltage, read and record:

  • Ratio error
  • Phase angle error

Also test under different load conditions — such as 25%, 50%, and 100% of rated burden.

Step 4: Analyze the Results

  • Compare the measured values with national standards or nameplate specifications.
  • If the error exceeds acceptable limits, the VT may need further inspection or repair.

3. Common Issues & How to Handle Them

4. Final Thoughts

As someone who's worked in this field for 8 years, here's what I’ve learned:

“The VT error test may seem detailed, but as long as the procedure is followed carefully and the setup is solid, it’s totally manageable.”

If you're new, try doing it with an experienced colleague at least once. And if you're seasoned, don’t get complacent — safety and accuracy always come first.If you ever run into issues during testing or feel unsure about certain steps, feel free to reach out. I’m happy to share more hands-on experience and tips.Here’s hoping every GIS voltage transformer runs safely and accurately!

— Oliver

Oliver Watts

Hey! I'm Oliver Watts, an electrical engineer in Inspection and Testing. With years of hands - on experience, I ensure electrical systems meet top safety and performance standards. Using advanced gear, I conduct diverse tests, easily spotting issues in both large - scale industrial and small - scale commercial setups. I love teaming up, sharing knowledge, and keeping up with industry regs. Also, I'm skilled at data analysis with software. If you're into electrical inspection or just want to chat engineering, reach out. Let's connect and explore!

What should be noted when selecting and installing GIS voltage transformers?
What should be noted when selecting and installing GIS voltage transformers?
In power systems, voltage transformers in GIS (Gas Insulated Switchgear) play a crucial role in voltage measurement and relay protection. Selecting the right model and installing it correctly is vital for the stable operation of the equipment. The following points should be noted regarding selection and installation.I. Key Points for Selection(1) Matching Rated ParametersVoltage Level: It must be consistent with the voltage level of the GIS system. For example, 110kV and 220kV GIS systems requir
James
07/08/2025
What are the causes of the breakdown and burning of the 35 kV GIS voltage transformer?
What are the causes of the breakdown and burning of the 35 kV GIS voltage transformer?
1. Accident Overview1.1 Structure and Connection of 35kV GIS Switchgear Voltage TransformerThe ZX2 gas-insulated double-bus switchgear, manufactured in March 2011 and officially put into operation in July 2012, is configured with two groups of bus voltage transformers (PTs) for each bus section. The two PT groups of the same bus section are designed in one switchgear cabinet with a width of 600 mm. The three-phase PTs are arranged in a triangular formation at the bottom of the cabinet.The PTs ar
Felix Spark
07/08/2025
An GIS Equipment Explosion Accident Caused by PT Secondary Wiring Errors
An GIS Equipment Explosion Accident Caused by PT Secondary Wiring Errors
1. Accident OverviewA newly - built 110kV substation’s GIS exploded during commissioning due to a PT secondary circuit short - circuit. Though the cause was simple, consequences were severe, warranting reflection.2. Accident ProcessOn the power - transmission day:The upper - level power supply charged the 110kV GIS (a combined appliance).20s after closing the incoming switch and first live - impacting the 110kV bus, white smoke emerged between the PT compartment and control cabinet.Within
Felix Spark
07/08/2025
Operation Method for PT Resonance in 500kV GIS Switching Station
Operation Method for PT Resonance in 500kV GIS Switching Station
1. Causes of ResonanceA 500kV GIS switching station is designed following the principle of “primary equipment intelligence and secondary equipment networking”. The PT high - voltage side has no disconnector and is directly connected to the bus GIS. Through the analysis of fault recording diagrams, when the 5021 circuit breaker opens, the fracture capacitance and PT form a series circuit. Moreover, the bus voltage, after being paralleled by the PT inductance, shows inductive character
James
07/08/2025
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!