Rockwill Company's SF6 Circuit Breaker Solution for Substations in the Ethiopian Highlands

05/13/2025

I.Project Background
The Ethiopian highlands feature high altitudes (average over 2,500 meters), extreme cold climates (winter temperatures as low as -30°C), and location within the seismically active East African Rift Zone. These conditions pose significant challenges to power equipment:

  1. SF6 Liquefaction Risk: At 0.6 MPa operating pressure, SF6 gas liquefies at -25°C. Extreme cold may cause liquefaction, leading to degraded insulation and loss of arc-extinguishing capability.
  2. Seismic Threats: The region experiences seismic intensities above 8 degrees. Traditional rigid connections are prone to mechanical damage or gas leakage due to geological activity.
  3. High Reliance on External Maintenance: Local technical expertise is limited, requiring long-term dependence on international contractors for maintenance, resulting in high costs and delayed responses.
    To address these challenges, Rockwill must design an SF6 circuit breaker solution tailored to high-altitude, cold, and seismic conditions while ensuring sustainable operation and maintenance.

II. Targeted SF6 Circuit Breaker Design and Installation

  1. Anti-Liquefaction Design
    • ​Built-in Heating Units: Drawing on proven solutions from China’s frigid regions, nickel-chromium alloy heating strips (800–1,200 W) are integrated at the base of the breaker’s porcelain insulator. Paired with temperature sensors for closed-loop control, this ensures SF6 gas remains above -18°C (exceeding the -25°C liquefaction point at 0.6 MPa).
    • ​Thermal Insulation Optimization: Nanogel aerogel material wraps the porcelain insulator and pipelines, reducing heat loss and improving heating efficiency by 30% in extreme cold.
  2. Seismic Reinforcement Design
    • ​Flexible Pipeline Connections: Corrugated SF6 gas pipelines allow axial displacement (±15 mm) and radial displacement (±10 mm), preventing seal failure from seismic stress concentration.
    • ​Reinforced Brackets and Isolation Bearings: Brackets use Q345B steel with cross-bracing, while friction pendulum isolation bearings at the base absorb 80% of seismic energy, reducing equipment acceleration response to below 0.3g.
  3. Localized Maintenance System
    • ​Technical Training Center: A training base in Addis Ababa provides bilingual (English/Amharic) courses focusing on SF6 gas detection, heating system calibration, and post-earthquake equipment evaluation.
    • ​Smart Monitoring System: IoT sensors monitor real-time gas pressure, temperature, and vibration. AI algorithms predict failures and generate maintenance orders, cutting manual inspections by 50%.

III. Expected Outcomes

  1. Enhanced Anti-Liquefaction Reliability: Heating systems stabilize arc-extinguishing chamber temperatures above -18°C, eliminating SF6 liquefaction risks. Annual circuit breaker failure rates drop below 0.5 incidents per unit.
  2. Seismic Compliance: Flexible connections and isolation designs enable the equipment to withstand seismic intensities of 8 degrees, with ≥95% functional integrity post-earthquake.
  3. Optimized Maintenance Costs: Local technician training cycles shorten to 3 months. Maintenance response time improves from 72 hours to 8 hours, reducing lifecycle costs by 40%.
  4. Environmental Adaptability Verified: The solution has passed -40°C low-temperature tests and simulated seismic platform trials, meeting the composite demands of East Africa’s high-altitude, low-temperature, and high-seismic environments.
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!