1. Solution Background
In 6kV~36kV distribution networks, delta-connected transformer windings lack a neutral grounding point. VZIMAN® Grounding Transformer addresses this by creating an artificial neutral through Z-type winding topology. This design prevents critical risks during single-phase ground faults, including:
Grounding Transformer enables:
2 . Core Advantages
2.1 Technical Leadership
Each phase splits into two reversely wound coils (Zig-Zag configuration), canceling zero-sequence flux → No-load losses reduced by 40% conventional transformers.
Zero-sequence impedance <10Ω(vs. >600Ω in star-delta transformers), enabling >90% arc suppression coil utilization.
Dry-type (AN/AF cooling) or oil-immersed (ONAN/ONAF)
Short-time withstand: 10s@3000A(customizable to 60s)
2.2 Multifunctional Integration
Replaces station service transformers by carrying secondary loads while providing neutral grounding, cutting equipment costs by 25%.
Generates 30–70V measurable voltagein full-cable networks (low unbalanced voltage).
Balanced 3-phase windings maintain accuracy under **>15% voltage unbalance**.
2.3 High-Reliability Engineering
Operational range: -40℃ ~ +40℃| Altitude: ≤1000m (insulation customizable for 4000m)
100% humidity tolerance with IP54+ protection
3. Grounding Transformer Application Scenarios
Scenario |
Grounding Transformer Solution |
6kV~10kV Distribution |
Provides low-impedance neutral (<10Ω) for delta systems → Direct arc suppression coil connection |
35kV+ Systems |
Cooperates with Y-winding transformers to optimize neutral grounding in hybrid grids |
Industrial Sites |
Custom windings for high unbalance/full-cable networks → Neutral voltage stabilization (30~70V) |
Smart Substations |
Integrated CT/VT + isolation switches → Real-time ground fault analytics |
4. Grounding Transformer Specifications
Parameter |
Value |
Type |
Zig-Zag (ZNyn) / Dry or oil-immersed |
Rated Voltage |
≤36kV |
Zero-Seq Impedance |
<10Ω (vs. industry avg. >600Ω) |
Cooling Methods |
ONAN (oil)/ONAF (oil+fan)/AN (dry)/AF (dry+fan) |
Note: All Grounding Transformers include IEC 60076-1/6 certification, de-energized tap changers, and HV/LV bushings.