• LVQB SF6 gas insulated current transformer
  • LVQB SF6 gas insulated current transformer
LVQB SF6 gas insulated current transformer
discuss personally
Model
LVQB-40.5
Basic info
Brand Wone
Model NO. LVQB SF6 gas insulated current transformer
Rated voltage 40.5kV
Series LVQB
Product Detail

Product introduction:
    LVQB series current transformers are SF6 gas insulated, inverted structure to meet the IEC/IEEE standard.The series connected transformer in the line has the functions of electricenergy measurement, metering, relay protec tion and transient protection.
Product features:
●The primary winding is of through type conductive rod structure with good dynamic and thermal stability.
●The maximum thermal stability current is 63kA/3s (when the primary winding is in series). 
●The primary winding passes through the center of the secondary winding without the influence of magnetic flux leakage, and the measurement accuracy reaches 0.1 and 0.2s
●The upper shell is of aluminum alloy welding structure, and the top is equipped with a metal explosion-proof disc. If the internal high-energy discharge occurs, when the gas pressure exceeds 1.0MP a, the explosion-proof disc will break, so as to achieve the purpose of pressure release, improve product safety, and there is no danger of explosion.
●The secondary winding is poured into the aluminum shield housing with organic materials, and the measuring and protection lines at the secondary side will not be subject to electrical attack due to insulation breakdown.
●The optimized electrode shielding structure improves the internal and external electric field distribution of the product, and the insulation performance is excellent. The local discharge test is conducted under the power frequency test voltage.
●The cast aluminum footing is directly cast on the external insulating bushing, and the bottom plate bolt is fixed with the footing from the bottom up to avoid water ingress and ponding from the base fastener. The secondary outlet box is cast with stainless steel or aluminum alloy. The dust-proof, waterproof and breathable sealing structure meets the requirements of IP55. 
●The secondary terminals for users to connect are Phoenix special terminal blocks, which are more convenient and fast to plug, pull and connect.
●The sealing ring is made of ethylene propylene diene monomer (EPDM) and imported fluor silicone rubber. It is suitable for areas with high and low temperature changes and harsh ambient temperatures. The annual air leak age rate is less than 0.5%.
●The product performance remains unchanged after rigorous transportation vibration test.
●The shell, base and junction box are all made of aluminum alloy. The nameplate is made of stainless steel. All exposed parts will never rust. The base is equipped with a density meter, which can display the gas pressure inside the transformer (the displayed value is automatically converted to the internal gas pressure at 20 ℃) and density. When the internal pressure of the transformer drops to the alarm pressure, it will provide a signal and require gas supplement.

LVQB SF6 gas insulated current transformer-2.png

LVQB SF6 gas insulated current transformer-3.png

Remark: Approximate dimensions and weights for special requirements, please consult us.

Know your supplier
Wone
Main Categories
High voltage/Low voltage/Wire cable/Instrument meters/New energy/Tester/Production equipment/Generator/Electrical fittings/Integrated Electrical Equipment
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$50,000,000
Professional Experience
1 years
Workplace
65666m²m²
占位
占位
Related Products
Related Knowledges
Failure Analysis and Design Optimization of Conventional Grounding Transformers
Failure Analysis and Design Optimization of Conventional Grounding Transformers
I. Core Cause of Damage: Electrodynamic Impact (Complying with GB/T 1094.5 / IEC 60076-5)The direct cause of high-voltage winding end collapse is the instantaneous electrodynamic impact induced by short-circuit current. When a single-phase grounding fault occurs in the system (such as lightning overvoltage, insulation breakdown, etc.), the grounding transformer, as the fault current path, withstands high-amplitude and steep-rise-rate short-circuit currents. According to Ampère's force law
Felix Spark
06/12/2025
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
1 Theoretical AnalysisIn distribution networks, grounding transformers serve two key roles: powering low - voltage loads and connecting arc - suppression coils at neutrals for grounding protection. Grounding faults, the most common distribution network fault, heavily impact transformers’ operating characteristics, causing sharp changes in electromagnetic parameters and status.To study transformers’ dynamic behaviors under single - phase grounding faults, build this model: Assume a tr
Felix Spark
06/12/2025
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
1 Classification of Neutral Grounding Methods for Solar Photovoltaic Power StationsInfluenced by differences in voltage levels and grid structures across regions, the neutral grounding methods of power systems are mainly categorized into non-effective grounding and effective grounding. Non-effective grounding includes neutral grounding via arc suppression coils and neutral ungrounded systems, while effective grounding comprises neutral solid grounding and neutral grounding via resistors. The sel
Dyson
06/12/2025
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
In a neutral-insulated three-phase power system, an earthing transformer provides an artificial neutral point, which can be solidly earthed or earthed via reactors/arc suppression coils. The ZNyn11 connection is typical, where zero-sequence magnetomotive forces in the inner/outer half-windings of the same core column cancel out, balancing fault currents in series windings and minimizing zero-sequence leakage flux/impedance.Zero-sequence impedance is critical: it determines fault current magnitud
Dyson
06/12/2025
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
The neutral grounding mode refers to the connection between the power system neutral point and ground. In China's 35 kV and below systems, common methods include ungrounded neutral, arc-suppression coil grounding, and small-resistance grounding. The ungrounded mode is widely used as it allows short-term operation during single-phase grounding faults, while small-resistance grounding has become mainstream for its fast fault removal and overvoltage limitation. Many substations install grounding tr
Felix Spark
06/12/2025
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
With the expansion of power system scale and the cableization process of urban power grids, the capacitive current in 6kV/10kV/35kV power grids has significantly increased (generally exceeding 10A). As power grids at this voltage level mostly adopt neutral ungrounded operation mode, and the distribution voltage side of main transformers is usually in delta connection, lacking a natural grounding point, the arc during ground faults cannot be reliably extinguished, necessitating the introduction o