• 110kV Porcelain housed Surge Arrester
110kV Porcelain housed Surge Arrester
discuss personally
Model
Y10WZ-300/727
HY10WZ-200/520
HY10WZ-100/260
HY5WS-10/30
Basic info
Brand Wone
Model NO. 110kV Porcelain housed Surge Arrester
Rated voltage 300kV
Continuous operating voltage 228kV
Lightning impulse residual voltage 727kV
Series Surge Arrester
Product Detail

Product introduction:

  • Surge arrester is also called overvoltage protector. It is connected in parallel with the protected electrical equipment. It can limit various overvoltage on electrical equipment, such as lightning overvoltage, operating overvoltage, etc., so as to protect the high voltage electrical from the damage of overvoltage.

  • Metaloxide varistor is used as the core component of surge arrester. The conductive mechanism of MOV is based on the non-linear volt-ampere characteristics of Schottky barrier model. The arrester is based on the principle of the non-linear volt-ampere characteristic of metal oxide varistor, which makes the arrester hold high resistance under the normal operating voltage of power system, which is equivalent to an insulator, and will not interfere with the normal operation of power system. When the overvoltage of power system endangers the safe operation of the system, the varistor triggers instantaneously and presents a low resistance. Forming a channel to release overvoltage energy, and clamp system voltage within the allowable range of the system to ensure the safe operation of the power system.

  • The arrester is porcelain-housed surge arrester. It has the advantages of high current impulse withstand capacity, large protection capacity and strong pollution resistance.

Parameter:

企业微信截图_17341409149808.png

 What are the structural characteristics of the porcelain shell arrester?

Porcelain Housing

The porcelain housing is a critical external structural component, offering excellent insulation properties and mechanical strength. The porcelain material can withstand electric field intensities of up to 110kV, preventing flashovers between internal components and the external environment. Additionally, the porcelain housing can endure certain mechanical stresses, such as wind and vibrations, protecting the sensitive internal components. Typically cylindrical in shape with a smooth surface, the porcelain housing helps reduce the adhesion of dust and contaminants. During manufacturing, it undergoes rigorous quality inspections to ensure there are no cracks or defects that could compromise its insulating properties.

Internal Components

The core internal component is the zinc oxide varistor disc. Under normal operating voltage, the zinc oxide varistor disc exhibits a high-resistance state, allowing only minimal current to pass through. When overvoltage occurs, its resistance drops sharply, forming a low-resistance path that allows the overvoltage-induced current to pass smoothly. These discs are made primarily from zinc oxide using specialized manufacturing processes, resulting in nonlinear volt-ampere characteristics that effectively limit the amplitude of overvoltages. Additionally, the internal structure may include connecting elements to link the varistor discs appropriately and auxiliary components like grading rings to ensure uniform voltage distribution across the discs during high-voltage conditions.

Sealing and Connection Structure

The porcelain-housed surge arrester features a robust sealing structure to prevent moisture, dust, and harmful gases from entering and affecting the performance of internal components. At both ends, there are connection structures for integrating the arrester into 110kV power lines. These connection parts are typically made of metal, capable of withstanding high voltages and large currents while providing excellent conductivity. This ensures that during an overvoltage event, current can flow smoothly into and out of the arrester.

Know your supplier
Wone
Main Categories
High voltage/Low voltage/Wire cable/Instrument meters/New energy/Tester/Production equipment/Generator/Electrical fittings/Integrated Electrical Equipment
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$50,000,000
Professional Experience
1 years
Workplace
65666m²m²
占位
占位
Related Products
Related Knowledges
Failure Analysis and Design Optimization of Conventional Grounding Transformers
Failure Analysis and Design Optimization of Conventional Grounding Transformers
I. Core Cause of Damage: Electrodynamic Impact (Complying with GB/T 1094.5 / IEC 60076-5)The direct cause of high-voltage winding end collapse is the instantaneous electrodynamic impact induced by short-circuit current. When a single-phase grounding fault occurs in the system (such as lightning overvoltage, insulation breakdown, etc.), the grounding transformer, as the fault current path, withstands high-amplitude and steep-rise-rate short-circuit currents. According to Ampère's force law
Felix Spark
06/12/2025
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
1 Theoretical AnalysisIn distribution networks, grounding transformers serve two key roles: powering low - voltage loads and connecting arc - suppression coils at neutrals for grounding protection. Grounding faults, the most common distribution network fault, heavily impact transformers’ operating characteristics, causing sharp changes in electromagnetic parameters and status.To study transformers’ dynamic behaviors under single - phase grounding faults, build this model: Assume a tr
Felix Spark
06/12/2025
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
1 Classification of Neutral Grounding Methods for Solar Photovoltaic Power StationsInfluenced by differences in voltage levels and grid structures across regions, the neutral grounding methods of power systems are mainly categorized into non-effective grounding and effective grounding. Non-effective grounding includes neutral grounding via arc suppression coils and neutral ungrounded systems, while effective grounding comprises neutral solid grounding and neutral grounding via resistors. The sel
Dyson
06/12/2025
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
In a neutral-insulated three-phase power system, an earthing transformer provides an artificial neutral point, which can be solidly earthed or earthed via reactors/arc suppression coils. The ZNyn11 connection is typical, where zero-sequence magnetomotive forces in the inner/outer half-windings of the same core column cancel out, balancing fault currents in series windings and minimizing zero-sequence leakage flux/impedance.Zero-sequence impedance is critical: it determines fault current magnitud
Dyson
06/12/2025
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
The neutral grounding mode refers to the connection between the power system neutral point and ground. In China's 35 kV and below systems, common methods include ungrounded neutral, arc-suppression coil grounding, and small-resistance grounding. The ungrounded mode is widely used as it allows short-term operation during single-phase grounding faults, while small-resistance grounding has become mainstream for its fast fault removal and overvoltage limitation. Many substations install grounding tr
Felix Spark
06/12/2025
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
With the expansion of power system scale and the cableization process of urban power grids, the capacitive current in 6kV/10kV/35kV power grids has significantly increased (generally exceeding 10A). As power grids at this voltage level mostly adopt neutral ungrounded operation mode, and the distribution voltage side of main transformers is usually in delta connection, lacking a natural grounding point, the arc during ground faults cannot be reliably extinguished, necessitating the introduction o